§ 13-196-110

Smoke detectors – Installation near sleeping rooms and in living levels

Every owner, manager or agent of any building, as described in Section 13-196-100, shall install, in every dwelling unit, not less than one approved smoke detector on the uppermost ceiling, not less than four inches from any wall, or on a wall, located from 12 inches from the ceiling, and within 15 feet of all rooms used for sleeping purposes, with not less than one detector per living level containing a habitable room or unenclosed heating plant.

(Prior code § 78-11; Amend Coun. J. 4-25-84, p. 6189; Amend Coun. J. 9-8-86, p. 33588)